2-wire programmable transmitter
- RTD or Ohm input
- High measurement accuracy
- 3-wire connection
- Programmable sensor error value
- For DIN form B sensor head mounting
Application
- Linearized temperature measurement with Pt100...Pt1000 or Ni100...Ni1000 sensor.
- Conversion of linear resistance variation to a standard analog current signal, for instance from valves or Ohmic level sensors.
Technical characteristics
- Within a few seconds the user can program PR5333D to measure temperatures within all RTD ranges defined by the norms.
- The RTD and resistance inputs have cable compensation for 3-wire connection.
Mounting / installation
- For DIN form B sensor head mounting.
Environmental Conditions
| Operating temperature | -40°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree (encl./terminal) | IP68 / IP00 |
Mechanical specifications
| Dimensions | Ø 44 x 20.2 mm |
| Weight approx. | 50 g |
| Wire size | 1 x 1.5 mm2 stranded wire |
| Screw terminal torque | 0.4 Nm |
| Vibration | IEC 60068-2-6 |
| 2...25 Hz | ±1.6 mm |
| 25...100 Hz | ±4 g |