Specifications
Range | TeSys |
---|---|
product name | TeSys LE |
Device short name | LE1D |
Product or component type | Enclosed DOL starter |
Device application | Standard |
Utilisation category | AC-3 |
Device composition | Thermal overload relay ordered separately Contactor |
Control type | Push-button start green I Push-button stop/reset red O |
Complementary
Motor power kW | 10 kW at 500 V AC 50/60 Hz 10 kW at 660/690 V AC 50/60 Hz 4 kW at 220/230 V AC 50/60 Hz 9 kW at 415 V AC 50/60 Hz 9 kW at 440 V AC 50/60 Hz 7.5 kW at 380/400 V AC 50/60 Hz |
---|---|
[Ith] Conventional free air thermal current | 17 A |
[Uc] control circuit voltage | 230 V AC 50/60 Hz |
Cable entry number | 2 ISO20 top 2 ISO25 top 2 ISO20 bottom 2 ISO25 bottom |
Width | 101 mm |
Height | 201 mm |
Depth | 153.5 mm |
Net weight | 1.015 kg |
Environment
Material | Polycarbonate |
---|---|
IP degree of protection | IP65 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 60529 |
Standards | IEC 60947-4-1 |
Ambient air temperature for operation | -5…40 °C |
Environmental characteristic | Standard environment |
Product certifications | UKCA |