Input Voltage | 24 Vdc nominal. Operating range is 18 to 32 Vdc Ripple cannot exceed 0.5 volt P-P |
Power Consumption | 4.0 watts nominal @ 24 Vdc; 7.5 watts maximum @ 24 Vdc; 10 watts maximum @ 32 Vdc |
Current Output | Linear 4-20 mA (current source/sink, isolated/non-isolated |
Warmup Time | Two minutes from cold power-up to normal mode; 1 hour minimum recommended. |
Relays (Opt.) | rated at 600 ohms maximum loop resistance @ 24 Vdc operating voltage |
Self-Diagnostic Test | All critical tests performed once per second. |
Detector Housing Material | Stainless Steel (316/CF8M Cast) |
Conduit Entry Options | Two entries, 3/4 inch NPT or 25 mm |
Dimensions | L = 9.3 in (23.62 cm), W = 5.2 in (13.21 cm), H = 4.6 in (11.68 cm) |
Accuracy | ±3% from 0 to 50% LFL, ±5% from 51 to 100% LFL |
Wiring Terminals | Field wiring screw terminals are UL/CSA rated for up to 14 AWG wire, and are DIN/VDE rated for 2.5 mm² wire. |