Current measuring transducer for 1 A and 5 A AC, the output signal 0...20 mA or 4...20 mA, can be configured using a DIP switch with an operating mode indication through an LED.
Maximum power dissipation for nominal condition | < 0.9 W (24 V DC) |
< 3.4 W (230 V AC) | |
Protective circuit | Surge protection; 35 V suppressor diode |
Step response (10-90%) | ≤ 300 ms |
200 ms | |
Maximum temperature coefficient | < 0.02 %/K |
Temperature coefficient, typical | < 0.015 %/K |
Maximum transmission error | ≤ 0.5 % (of nominal range value under nominal conditions) |
Reverse polarity protection | yes |
Rated insulation voltage | 300 V AC (to earth) |
Dimensions
Width | 22.5 mm |
Height | 104 mm |
Depth | 114.5 mm |
Ambient Conditions
Degree of protection | IP20 |
Ambient temperature (operation) | -20 °C ... 65 °C |
-4 °F ... 149 °F | |
Ambient temperature (storage/transport) | -40 °C ... 85 °C (-40 °F ... 185 °F) |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |