Range | TeSys |
---|---|
Product name | TeSys GS |
Device short name | GS1 DD |
Product or component type | Switch-disconnector-fuse |
Device application | Protection |
Poles description | 3P |
Protected poles description | 3t |
Contacts type and composition | 3 NO |
[Ith] conventional free air thermal current | 32 A (at 40 °C) |
[Ie] rated operational current | 20 A at 440 V 2 poles in series per phase DC-23A 20 A at 440 V 2 poles in series per phase DC-23B 32 A at 400 V AC-23A 32 A at 400 V AC-23B 32 A at 500 V AC-23A 32 A at 500 V AC-23B 32 A at 690 V AC-23A 32 A at 690 V AC-23B |
Fuse type | NFC |
Fuse size | 10 x 38 mm |
Network type | AC DC |
Network frequency | 50/60 Hz |
Environment
Type of operating handle | Direct frontal External left side External right side External frontal |
---|---|
Mounting support | Plate Rail |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 8 kV |
Rated operational power in W | 15 kW at 400 V 18.5 kW at 500 V 25 kW at 690 V |
Making capacity | 320 A at 400 V AC-23B |
Breaking capacity | 256 A at 400 V (AC-23B) |
Short-circuit withstand | 5.5 kA |
Mechanical durability | 20000 cycles |
Electrical durability | 1500 cycles AC-23A 1500 cycles AC-23B 300 cycles DC-23A 300 cycles DC-23B |
Connections - terminals | Power circuit: screw-clamp terminals2.5…16 mm² flexible |
[Icm] rated short-circuit making capacity | 100 kA at 400 V with protection by gG fuses |