Cart
Your cart is currently empty.

LC1-D65AM7

-
+

Contactor, TeSys Deca, 3P(3 NO), AC-3/AC-3e, <=400V, 65A, 220V AC 50/60Hz coil, screw clamp terminals

 

Specifications

Range TeSys
TeSys Deca
Range of product TeSys Deca
Product or component type Contactor
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-4
AC-1
AC-3
AC-3e
Polishing description Threesome
[Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 220 V AC 50/60 Hz


Complementary

Motor power kW 11 kW at 400 V AC 50/60 Hz (AC-4)
18.5 kW at 220...230 V AC 50/60 Hz (AC-3)
30 kW at 380...400 V AC 50/60 Hz (AC-3)
37 kW at 500 V AC 50/60 Hz (AC-3)
37 kW at 660...690 V AC 50/60 Hz (AC-3)18.5 kW at 220...230 V AC 50/60 Hz (AC-3e)30 kW at 380...400 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3e)37 kW at 500 V AC 50/60 Hz (AC-3)

18.5 kW at 220...230 V AC 50/60 Hz (AC-3e)

30 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
5 hp at 115 V AC 50/60 Hz for 1 phase motors
10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 10 A (at 60 °C) for signalling circuit
80 A (at 60 °C) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 640 A 40 °C - 10 s for power circuit
900 A 40 °C - 1 s for power circuit
110 A 40 °C - 10 min for power circuit
260 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
125 A gG at <= 690 V coordination type 1 for power circuit
125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole 9.6 W AC-1
6.3 W AC-3
6.3 W AC-3e
[Ui] rated insulation voltage Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category III
pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability 6 Mcycles
Electrical durability 1.4 Mcycles 80 A AC-1 at Ue <= 440 V
1.45 Mcycles 65 A AC-3 at Ue <= 440 V
1.45 Mcycles 65 A AC-3e at Ue <= 440 V
Control circuit type AC at 50/60 Hz standard
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc (-40... 70 °C):d rop-out AC 50/60 Hz
0.8...1.1 Uc (-40... 60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40 °C) 60 °C):operational AC 60 Hz
1...1.1 Uc (60 °C) 70 °C):operational AC 50/60 Hz
Inrush power in VA 140 VA 60 Hz cos fi 0.75 (at 20 °C)
160 VA 50 Hz cos fi 0.75 (at 20 °C)
Hold-in power consumption in VA 13 VA 60 Hz cos phi 0.3 (at 20 °C)
15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 4… 5 W at 50/60 Hz
Operating time 4...19 ms opening
12...26 ms closing
Maximum operating rate 3600 cyc/h at 60 °C
Connections - terminals Control circuit: screw clamp terminals 2 1... 2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1... 4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1... 4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1... 4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1... 4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1... 4 mm² - cable stiffness: solid without cable end
Power circuit: EverLink BTR screw connectors 1 1... 35 mm² - cable stiffness: flexible without cable end
Power circuit: EverLink BTR screw connectors 2 1... 25 mm² - cable stiffness: flexible without cable end
Power circuit: EverLink BTR screw connectors 1 1... 35 mm² - cable stiffness: flexible with cable end
Power circuit: EverLink BTR screw connectors 2 1... 25 mm² - cable stiffness: flexible with cable end
Power circuit: EverLink BTR screw connectors 1 1... 35 mm² - cable stiffness: solid without cable end
Power circuit: EverLink BTR screw connectors 2 1... 25 mm² - cable stiffness: solid without cable end
Tightening torque Control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver Philips No 2
Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25... 35 mm² hexagonal screw head 4 mm
Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1... 25 mm² hexagonal screw head 4 mm
Control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver pozidriv No 2
Power circuit: 2.5 N.m - on EverLink BTR screw connectors - with screwdriver pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting support Rail
Plate