Technical Specifications for LRD340
- Product Type: Thermal overload relay
- Product Range: TeSys LRD / TeSys Deca
- Network Type: AC
- Network Frequency: 0...400 Hz
- Thermal Protection Adjustment Range: 30...40 A
- Rated Insulation Voltage (Ui): 600 V (UL/CSA) / 690 V (IEC 60947-4-1)
- Rated Impulse Withstand Voltage (Uimp): 6 kV
- Tripping Class: Class 10A conforming to IEC 60947-4-1
- Auxiliary Contact Composition: 1 NO + 1 NC
- Permissible Current: 3 A at 120 V AC-15 (NC) / 0.22 A at 125 V DC-13 (NC)
- Short-Circuit Protection: 40 A gG for signaling circuit / 80 A gG for power circuit
- Control Type: Red push-button (Stop) / Blue push-button (Reset)
- Reset Mode: Manual or Automatic
- Connection Terminals: EverLink BTR screw connectors
- Tightening Torque: Power circuit: 5 N.m / Control circuit: 1.7 N.m
- Mounting Support: Direct under contactor / Independent mounting with accessories
- Compatible Contactors: LC1D40A, LC1D50A, LC1D65A
- Standards: IEC 60947-4-1, IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1
- Product Certifications: CE, UL, CSA, CCC, EAC, UKCA
- IP Degree of Protection: IP20 conforming to IEC 60529
- Ambient Air Temperature for Operation: -20...60 °C without derating